Item |
Specifications |
Product transition selection (1) | Before replacement(connector 40P ×2):C500-OD213 |
After replacement(connector 40P ×2):RY41NT2P ×2(*1)(*2)(*3) |
Product transition selection (2) | Before replacement(FCN connector 40P):C200H-OD218(*4) |
After replacement(FCN connector 40P):RY41NT2P(*5) |
Product transition selection (3) | Before replacement(FCN connector 40P):C200H-OD21B(*4) |
After replacement(FCN connector 40P):RY41PT1P |
Product transition selection (4) | Before replacement(connector 40P ×2):C200H-OD219(*4) |
After replacement(connector 40P ×2):RY41NT2P × 2(*1)(*5) |
Product transition selection (5) | Before replacement(FCN connector 40P):CS1W-OD231 |
After replacement(FCN connector 40P):RY41NT2P(*6)(*7) |
Product transition selection (6) | Before replacement(FCN connector 40P):CS1W-OD232 |
After replacement(FCN connector 40P):RY41PT1P(*8)(*9) |
Product transition selection (7) | Before replacement(connector 40P ×2):CS1W-OD261 |
After replacement(connector 40P ×2):RY41NT2P × 2(*6)(*10) |
Product transition selection (8) | Before replacement(connector 40P ×2):CS1W-OD262 |
After replacement(connector 40P ×2):RY41PT1P × 2(*6)(*9)(*11) |
Product transition selection (9) | Before replacement(FCN connector 40P):CS1W-MD261(Output) |
After replacement(FCN connector 40P):RY41NT2P(*6)(*7) |
Product transition selection (10) | Before replacement(FCN connector 40P):CS1W-MD262(Output) |
After replacement(FCN connector 40P):RY41PT1P(*6)(*9) |
Product transition selection (11) | Before replacement(FCN connector 40P):CQM1-OD213 |
After replacement(FCN connector 40P):RY41NT2P(*12) |
Product transition selection (12) | Before replacement(FCN connector 40P):CQM1-OD216 |
After replacement(FCN connector 40P):RY41PT1P |
Product transition selection (13) | Before replacement(FCN connector 40P):CJ1W-OD231 |
After replacement(FCN connector 40P):RY41NT2P(*6)(*14) |
Product transition selection (14) | Before replacement(connector 40P ×2):CJ1W-OD261 |
After replacement(connector 40P ×2):RY41NT2P x 2(*6)(*14) |
Product transition selection (15) | Before replacement (FCN connector 40P):CJ1W-MD261 (Output) |
After replacement(FCN connector 40P):RY41NT2P(*6)(*14) |
Product transition selection (16) | Before replacement(connector 40P ×2):JAMSC-B2604 |
After replacement(connector 40P ×2):RY41NT2P×2(*13) |
Precautions | *1:Two MELSEC iQ-R series modules and two conversion adapters are required. |
*2:When replacing the existing module with two MELSEC iQ-R series modules and two conversion adapters, the mounting height of the existing wiring changes. Check the existing wiring length. |
*3:If the response speed of the RY41NT2P does not satisfy the specifications of the existing module, consider replacing the module with the high-speed output module (RY41NT2H). |
*4:SYSMAC C series modules with "-N" at the end of their model name are not listed because only the difference is whether a connector is included or not. |
*5:When a rated load voltage of 5VDC is used, the voltage needs to be changed to 12 or 24VDC. |
*6:Since the number of points per common changes (16 points/common → 32 points/common), check the common terminal connection of the module before replacement. |
*7:If the existing module uses a different power supply for each 16-point group, consider rewiring to two RY40NT5Ps. |
*8:If the existing module uses a different power supply for each 16-point group, consider rewiring to two RY40PT5Ps. |
*9:If the current capacity of the RY41PT1P does not satisfy the specifications of the existing module, consider replacing the module with the high-speed input module (RY41PT2H). |
*10:Two MELSEC iQ-R series modules and two conversion adapters are required. If the existing module uses a different power supply for each 16-point group, consider rewiring to four RY40NT5Ps. |
*11:If the existing module uses a different power supply for each 16-point group, consider rewiring to four RY40PT5Ps. |
*12:When a rated load voltage of 5VDC is used, the voltage needs to be changed to 12 or 24VDC. Or, consider replacing the module with the high-speed output module (RY41NT2H). |
*13:A conversion adapter for replacing the OMRON SYSMAC C series with the MELSEC iQ-R series is used. |
*14:If the existing module uses a different power supply for each 16-point group, consider rewiring to multiple RY40NT5P. |