For MELSEC-L CPU module with built-in I/O function (positioning function)

FA-PT1LBD

Features

  • Product overview:
    The junction terminal block helps signal transmissions between a programmable controller and devices such as sensors in connection methods suitable for applications.
    Merit.1
    This product converts outputs into the differential driver outputs, improving the external-noise resistance.
    Merit.2
    The maximum wiring length to a drive unit is 10m, which allows more flexible installation of units.
Sales status On sale

Basic specifications

Item Specifications
Model FA-PT1LBD
Category Time and wire saving devices
Connected device Programmable controller
Series of connected devices MELSEC-L
Product category Junction terminal block for programmable controller
Terminal block type Screw terminal type

Specifications

General specifications

Item Specifications
Operating ambient temperature 0 to 55℃
Storage ambient temperature -25 to 75℃
Operating ambient humidity 5 to 95%RH, no condensation
Storage ambient humidity 5 to 95%RH, no condensation
Vibration resistance ( With intermittent vibration ) 5 to 8.4Hz : Half amplitude 3.5mm
8.4 to 150Hz : Acceleration 9.8m/s2
Number of sweeps : 10 times in each direction X, Y, and Z
Vibration resistance ( With continual vibration ) 5 to 8.4Hz : Half amplitude 1.75mm
8.4 to 150Hz : Acceleration 4.9m/s2
Shock resistance 147m/s2, 3 times in each direction X, Y, and Z(Applicable standards : JIS B 3502, IEC61131-2)
Operating atmosphere Free of corrosive gases
Operating altitude *1 2000m or less
Installation location Inside the control panel
Overvoltage category *2 II or less
Pollution degree *3 2 or less
Precautions *1 Do not use or store the module under pressure higher than the atmospheric pressure at an altitude of 0 meters. Doing so may cause malfunction. When using
the module under pressure, please consult your local Mitsubishi Electric representative.
*2 This indicates the assumption that the equipment is connected to a power distribution system, ranging from a public electrical power distribution network down to machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for equipment with the rated voltage of up to 300V is 2500V.
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. In pollution degree 2, only nonconductive
pollution occurs. A temporary conductivity caused by condensation must be expected occasionally.


Product specifications

Item Specifications
PULSE F/R output specifications : Output Differential drivers equivalent to the AM26C31
PULSE F/R output specifications : Maximum output pulse 200kpps
PULSE F/R output specifications : Pulse width 2.0us or more
PULSE F/R output specifications : Maximum connection distance with drive module 10m
Power supply for command pulse signals 24V+-10%, 50mA or less
PG0/CHG/DOG/FLS/RLS input specifications Depends on MELSEC-L CPU module with built-in I/O function (positioning function)
READY input specifications Depends on MELSEC-L CPU module with built-in I/O function (positioning function)
CLEAR output specifications Depends on MELSEC-L CPU module with built-in I/O function (positioning function)
Module power supply 24VDC+-10% (ripple ratio: within 5%)
Module current consumption Approx. 40mA at 24VDC (not including current consumption of programmable controller)
Terminal block : Terminal screw M3 screws, number of terminals: 25P, 7.62mm pitch, spring-up screw with finger protection cover
Terminal block : Applicable wire, tightening torque 0.5 to 1.25mm2, 58.8 to 88.2N-cm (6 to 9kgf·cm)
Module installation : Screw type M4 × 0.7mm × 16mm or more, tightening torque: 78 to 108N-cm (8 to 11kgf·cm)
Module installation : DIN rail installation Applicable DIN rails: TH35-7.5Fe, TH35-7.5AL (IEC 60715 compliant)
Withstand voltage, insulation resistance Between power supply and signal: 500VAC for 1 minute, 10MΩ or more
Weight Approx. 170g
Precautions *: For wiring to the terminal block, refer to the manual of the MELSEC-L CPU module to be connected, published by Mitsubishi Electric.

External Dimensions・Product CAD Data

External Dimensions

Product CAD Data

Wiring diagrams and connection examples・Note

Wiring diagrams and connection examples

N/A

Name Filename

Other Technical Information

N/A

Name Filename

Precautions for use

N/A

Name Filename

Catalogs・New Product Releases

* The table can be scrolled to the right.

Name Language Document No. Release date
FA Goods General Catalog Digest edition(28MB) English MEIC198E_209-B March 2024
FA关联产品 综合目录 摘要版(29MB) Simplified Chinese MEIC199C_209-B March 2024
FA Goods General Catalog Time and Wire Saving Devices(79MB) English MEIC202E_20Z-E November 2024

Manual

* The table can be scrolled to the right.

Name Language Document No. Release date
User’s Manual(372KB) English 50D-FA9010-135E-C September 2014
EMC and Low Voltage Directives Compliant Manual(256KB) English 50D-FA9010-108E-G December 2023

Technical information(Technical News)

N/A

* The table can be scrolled to the right.

Name Language Document No. Release date

Downloads

N/A

Profile/module FB (function block)

Name Filename

Control & Communication System Profile CSP+

Name Filename

Sample program

Name Filename

Video

N/A

Related products

Connection cables

Model Length Name Overview
FA-SCBL10FM2LV-LB 1.0m Connection cable between MELSEC-L CPU module with built-in I/O and junction terminal block Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.

Related products

N/A