- Spring clamp type, 16 points, independent (positive common), Unit with relay modules (24 V DC, NO contact)
FA1-TH16X24RA1L20S1E
- Features
- Specifications
- External Dimensions・
Product CAD Data - Wiring diagrams and connection examples・
Note - Catalogs・
New Product Releases - Manual
- Technical information
(Technical News) - Downloads
- Video
- Related products
Features
-
- Product overview:
-
Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.
- Merit.1
- Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.
- Merit.2
- Output modules (relay/triac/transistor) can be combined flexibly.
- Merit.3
- When a 64-point output module is used, output conversion for a maximum of 64 points can be made per one slot.
- Merit.4
- Sockets enable relay modules to be replaced individually. (Easy maintenance)
- Merit.5
- The spring clamp terminal block does not require screws.
Wires can be easily pushed into the conductive terminals without using
a screwdriver.
Sales status | On sale |
---|
Basic specifications
Item | Specifications | |
---|---|---|
Model | FA1-TH16X24RA1L20S1E | |
Category | Time and wire saving devices | |
Connected device | Programmable controller | |
Series of connected devices | MELSEC iQ-R | |
MELSEC iQ-F | ||
MELSEC-Q | ||
MELSEC-F | ||
MELSEC-L | ||
Product category | Digital signal converter (terminal module) | |
Terminal block type | Spring clamp type | |
Delivery date | - |
Specifications
General specifications
Item | Specifications | |
---|---|---|
Operating ambient temperature | -20 to 55℃ | |
Storage ambient temperature | -25 to 75℃ | |
Operating ambient humidity | 5 to 95%RH, no condensation | |
Storage ambient humidity | 5 to 95%RH, no condensation | |
Vibration resistance ( With intermittent vibration ) | 5 to 8.4Hz : Half amplitude 3.5mm | |
8.4 to 150Hz : Acceleration 9.8m/s2 | ||
Number of sweeps : 10 times in each direction X, Y, and Z | ||
Vibration resistance ( With continual vibration ) | 5 to 8.4Hz : Half amplitude 1.75mm | |
8.4 to 150Hz : Acceleration 4.9m/s2 | ||
Shock resistance | 147m/s2, 3 times in each direction X, Y, and Z(Applicable standards : IEC61131-2) | |
Operating atmosphere | Free of corrosive gases | |
Operating altitude *1 | 2000m or less | |
Installation location | Inside control panel(Indoor use) | |
Overvoltage category *2 | II or less | |
Pollution degree *3 | 2 or less | |
Precautions | *1 Do not use or store the module under pressure higher than the atmospheric pressure at an altitude of 0 meters. Doing so may cause malfunction. When using the module under pressure, please consult your local Mitsubishi Electric representative. |
|
*2 This indicates the assumption that the equipment is connected to a power distribution system, ranging from a public electrical power distribution network down to machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for equipment with the rated voltage of up to 300V is 2500V. | ||
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. In pollution degree 2, only nonconductive pollution occurs. A temporary conductivity caused by condensation must be expected occasionally. |
Product specifications
Item | Specifications | |
---|---|---|
Connected programmable controller | Positive common, 24VDC input module | |
No. of points | 16 | |
Isolation method | Relay | |
Rated input voltage/current | Voltage: 24 V DC (CLASS 2 or SELV + LIM), Current: Approx. 10 mA (24 V DC) | |
Maximum number of simultaneous on points | 100% (5-directional attachment) | |
On voltage/On current | 19.2 V DC or more/8.1 mA or more | |
Off voltage/Off current | 2.4 V DC or less/1.0 mA or less | |
Input impedance | Approx. 2.2 kΩ | |
Response time ( Off → On ) | 10ms or less (excluding programmable controller response time) | |
Response time ( On → Off ) | 12ms or less (excluding programmable controller response time) | |
Minimum switching load | 24VDC, 1mA or more | |
Maximum switching frequency | 1800 times/hour (ON for 1 second or more and OFF for 1 second or more) | |
Mechanical life | 20 million times or more | |
Electrical life *1 | 24 V DC 100 mA for one hundred thousand times or more (contact side) | |
Wiring method for common | Independent common ( Positive common input type ) |
|
External power supply | 24 V DC +-10% (ripple rate within 5%, CLASS 2 or SELV + LIM) | |
Module current consumption | Approx. 10 mA at 24 V DC (not including programmable controller current draw) | |
Withstand voltage, insulation resistance | Between inputs and between external power supply and input: 510 V AC rms/min. (altitude 0 to 2000 m) for one minute, 10 MΩ or more | |
Noise immunity | Simulator noise 500 Vp-p, noise width 1 us (measured by a noise simulator with a noise frequency of 25 to 60 Hz) | |
Operation display | The LED is lit when the power and input turn ON. | |
Socket | Attached (relay modules replaceable) | |
No. of times to replace module | 50 | |
Module mixing | Possible | |
Number of terminals | 52 points (power supply: 4 points, input: 48 points) | |
Applicable wire *2 | Without ferrule Stranded or solid wire: 0.2 to 1.5 mm2 (24 to 16 AWG) With ferrule Stranded or solid wire: 0.08 to 0.75 mm2 (28 to 18 AWG) |
|
Wire strip length | 8mm | |
Module installation *3 | Screw type | M4 × 0.7 mm × 22 mm or longer Tightening torque: 78 to 118 N-cm (8 to 12 kgf-cm) |
DIN rail | Applicable DIN rail: TH35-7.5Fe, TH35-7.5AL (JIS C 2812 compliant) | |
Weight | Approx. 220 g | |
Precautions | Evaluation for UL certification is conducted 6000 times. | |
For UL certification, suitable for field wiring when a ferrule is not used. | ||
Evaluation for UL certification is conducted a DIN rail installation. |
External Dimensions・Product CAD Data
External Dimensions
N/A
Name | Filename |
---|
Product CAD Data
N/A
Name | Filename |
---|
Wiring diagrams and connection examples・Note
Wiring diagrams and connection examples
N/A
Name | Filename |
---|
Other Technical Information
N/A
Name | Filename |
---|
Precautions for use
N/A
Name | Filename |
---|
Catalogs・New Product Releases
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|---|---|---|
MELSEC系列专用 中继端子排(861KB) | Simplified Chinese | MEIC230C_22X-A | February 2025 |
Digital Signal Converters (Terminal Modules)(3MB) | English | MEIC224E_226-C | February 2025 |
数字信号转换器(终端模块)(3MB) | Simplified Chinese | MEIC234C_236-A | February 2025 |
FA Goods General Catalog Digest edition(28MB) | English | MEIC198E_209-B | March 2024 |
FA关联产品 综合目录 摘要版(29MB) | Simplified Chinese | MEIC199C_209-B | March 2024 |
FA Goods General Catalog Time and Wire Saving Devices(79MB) | English | MEIC202E_20Z-E | November 2024 |
Manual
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|---|---|---|
User's Manual(4MB) | English | 50D-FG0233E-C | June 2022 |
Technical information(Technical News)
N/A
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|
Downloads
N/A
Profile/module FB (function block)
Name | Filename |
---|
Control & Communication System Profile CSP+
Name | Filename |
---|
Sample program
Name | Filename |
---|
Video
N/A
Related products
Connection cables
Model | Length | Name | Overview |
---|
Related products
N/A