- [Input type] Conversion adapter (1 input - 2 current outputs supported)
FA-ATKAA8XM
- Features
- Specifications
- External Dimensions・
Product CAD Data - Wiring diagrams and connection examples・
Note - Catalogs・
New Product Releases - Manual
- Technical information
(Technical News) - Downloads
- Video
- Related products
Features
-
- Product overview:
-
Analog signals from the connected devices such as sensors can be
converted to signals suitable for a programmable controller (example:
from a temperature signal to a voltage signal).
Data from sensors can be visualized easily, and small-scale IoT can be
introduced.
- Merit.1
- This product is used with a module installation base unit (FA-ATKB8XTB).
- Merit.2
- Reliability is improved by isolation between output 1 (programmable controller side) and output 2 (recorder connected side).
Sales status | On sale |
---|
Basic specifications
Item | Specifications | |
---|---|---|
Model | FA-ATKAA8XM | |
Category | Time and wire saving devices | |
Connected device | Programmable controller | |
Series of connected devices | MELSEC iQ-R | |
MELSEC-Q | ||
MELSEC-L | ||
MELSEC iQ-F | ||
MELSEC-F | ||
CC-Link IE TSN | ||
CC-Link IE Field | ||
CC-Link | ||
Other PLC | ||
Computers from various manufacturers | ||
Product category | Analog signal converter | |
Terminal block type | Screw terminal type | |
Delivery date | - |
Specifications
General specifications
Item | Specifications | |
---|---|---|
Operating ambient temperature | 0 to 55℃ | |
Storage ambient temperature | -25 to 75℃ | |
Operating ambient humidity | 5 to 95%RH, no condensation | |
Storage ambient humidity | 5 to 95%RH, no condensation | |
Vibration resistance ( With intermittent vibration ) | 5 to 8.4Hz : Half amplitude 3.5mm | |
8.4 to 150Hz : Acceleration 9.8m/s2 | ||
Number of sweeps : 10 times in each direction X, Y, and Z | ||
Vibration resistance ( With continual vibration ) | 5 to 8.4Hz : Half amplitude 1.75mm | |
8.4 to 150Hz : Acceleration 4.9m/s2 | ||
Shock resistance | 147m/s2, 3 times in each direction X, Y, and Z(Applicable standards : JIS B 3502, IEC61131-2) | |
Operating atmosphere | Free of corrosive gases | |
Operating altitude *1 | 2000m or less | |
Installation location | Inside the control panel | |
Overvoltage category *2 | II or less | |
Pollution degree *3 | 2 or less | |
Precautions | *1 Do not use or store the module under pressure higher than the atmospheric pressure at an altitude of 0 meters. Doing so may cause malfunction. When using the module under pressure, please consult your local Mitsubishi Electric representative. |
|
*2 This indicates the assumption that the equipment is connected to a power distribution system, ranging from a public electrical power distribution network down to machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for equipment with the rated voltage of up to 300V is 2500V. | ||
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. In pollution degree 2, only nonconductive pollution occurs. A temporary conductivity caused by condensation must be expected occasionally. |
Product specifications
Item | Specifications | |
---|---|---|
No. of points | 8 (8 channel) | |
Input : Input signal | 1 to 5V (module output) | |
Accuracy(percentage of full scale) : Reference accuracy | +-0.1% or less (surrounding air temperature: 25°C+-5°C)( The table shows the specifications for an adapter alone. The accuracy of modules to be mounted should be added. ) *1 | |
Accuracy(percentage of full scale) : Temperature characteristics | +-0.015%/°C or less | |
Output 1(OUT1) (programmable controller side) : Interface | 20-pin MIL connector | |
Output 1(OUT1) (programmable controller side) : Output signal | 4 to 20mA | |
Output 1(OUT1) (programmable controller side) : Output allowable load resistance | 250 to 350Ω | |
Output 1(OUT1) (programmable controller side) : Isolation between input and output | Not provided | |
Output 1(OUT1) (programmable controller side) : Isolation between output channels | Not provided | |
Output 2 (OUT2) : Interface | Through FA-ATKB8XTB OUT2 (M3 spring-up screws, 7.62mm pitch) | |
Output 2 (OUT2) : Output signal | 4 to 20mA | |
Output 2 (OUT2) : Output allowable load resistance | 600Ω or less *Operating temperature range restricted | |
Output 2 (OUT2) : Isolation between input and output | Transformer | |
Output 2 (OUT2) : Isolation between output channels | Provided | |
Response speed | 10ms or less( Time from when a startup pulse is input until the output level reaches 90% ) *2 | |
Power supply | 24VDC+-10% (Supplied from the installation base unit) | |
Current consumption (24VDC) | 310mA or less | |
Withstand voltage, insulation resistance | Between input, all outputs for output 1, each channel for output 2, and power supply: 750VAC for 1 minute, 10MΩ or more |
|
Mounting screw tightening torque for installation base unit | 36 to 48N・cm (3.7 to 4.8kgf・cm) | |
Weight | Approx. 200g | |
Precautions | When connecting cables to the module, push the cable connector until it is locked. Failure to do so may cause poor contact. | |
A pass-through module (FA-ATFTMXY) can be used for voltage input only. | ||
When connecting the product with a programmable controller, confirm that the product configuration is correct. Connection based on a wrong configuration may cause a failure or malfunction. | ||
*1 The table shows the specifications for an adapter alone. The accuracy of modules to be mounted should be added. | ||
*2 Time from when a startup pulse is input until the output level reaches 90% |
External Dimensions・Product CAD Data
External Dimensions
N/A
Name | Filename |
---|
Product CAD Data
N/A
Name | Filename |
---|
Wiring diagrams and connection examples・Note
Wiring diagrams and connection examples
N/A
Name | Filename |
---|
Other Technical Information
N/A
Name | Filename |
---|
Precautions for use
N/A
Name | Filename |
---|
Catalogs・New Product Releases
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|---|---|---|
Analog Signal Converters(2MB) | English | MEIC220E_21Y-B | February 2025 |
模拟信号转换器 (2MB) | Simplified Chinese | MEIC235C_23X-A | February 2025 |
FA Goods General Catalog Digest edition(28MB) | English | MEIC198E_209-B | March 2024 |
FA关联产品 综合目录 摘要版(29MB) | Simplified Chinese | MEIC199C_209-B | March 2024 |
FA Goods General Catalog Time and Wire Saving Devices(79MB) | English | MEIC202E_20Z-E | November 2024 |
Manual
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|---|---|---|
User's Manual Analog Signal Conversion Module (Input type)(2MB) | English | 50D-FA9010-122E-G | December 2023 |
EMC and Low Voltage Directives Compliant Manual(256KB) | English | 50D-FA9010-108E-G | December 2023 |
Technical information(Technical News)
N/A
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|
Downloads
N/A
Profile/module FB (function block)
Name | Filename |
---|
Control & Communication System Profile CSP+
Name | Filename |
---|
Sample program
Name | Filename |
---|
Video
N/A
Related products
Connection cables
Model | Length | Name | Overview |
---|
Related products
N/A