- 16-point relay output (16-point independent common)
FA-FXTH16YRA20
- Features
- Specifications
- External Dimensions・
Product CAD Data - Wiring diagrams and connection examples・
Note - Catalogs・
New Product Releases - Manual
- Technical information
(Technical News) - Downloads
- Video
- Related products
Features
-
- Product overview:
-
Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.
- Merit.1
- This module converts Mitsubishi Electric micro programmable controller iQ-F/F series connector-type output signals (transistor outputs) into 16-point N/O contact relay output terminal block (2A/point) outputs.
- Merit.2
- Cross-head screws of terminals are spring-up screws, making round solderless terminal installation easy.
- Merit.3
- The product can be installed using a DIN rail or screws.
Sales status | On sale |
---|
Basic specifications
Item | Specifications | |
---|---|---|
Model | FA-FXTH16YRA20 | |
Category | Time and wire saving devices | |
Connected device | Programmable controller | |
Series of connected devices | MELSEC iQ-F | |
MELSEC-F | ||
Product category | Digital signal converter (terminal module) | |
Terminal block type | Screw terminal type | |
Delivery date | - |
Specifications
General specifications
Item | Specifications | |
---|---|---|
Operating ambient temperature | -20 to 55℃ | |
Storage ambient temperature | -25 to 75℃ | |
Operating ambient humidity | 5 to 95%RH, no condensation | |
Storage ambient humidity | 5 to 95%RH, no condensation | |
Vibration resistance ( With intermittent vibration ) | 5 to 8.4Hz : Half amplitude 3.5mm | |
8.4 to 150Hz : Acceleration 9.8m/s2 | ||
Number of sweeps : 10 times in each direction X, Y, and Z | ||
Vibration resistance ( With continual vibration ) | 5 to 8.4Hz : Half amplitude 1.75mm | |
8.4 to 150Hz : Acceleration 4.9m/s2 | ||
Shock resistance | 147m/s2, 3 times in each direction X, Y, and Z(Applicable standards : JIS B 3502, IEC61131-2) | |
Operating atmosphere | Free of corrosive gases | |
Operating altitude *1 | 2000m or less | |
Installation location *2 | Inside the control panel (Indoor use) | |
Overvoltage category *3 | II or less | |
Pollution degree *4 | 2 or less | |
Precautions | *1 Do not use or store the module under pressure higher than the atmospheric pressure at an altitude of 0 meters. Doing so may cause malfunction. When using the module under pressure, please consult your local Mitsubishi Electric representative. |
|
*2 Install the module in a control panel that satisfies both of the following: a protection degree of IP20, UL50 Type 1 or higher. Design the control panel suitable for the environment if necessary. | ||
*3 This indicates the assumption that the equipment is connected to a power distribution system, ranging from a public electrical power distribution network down to machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for equipment with the rated voltage of up to 300V is 2500V. | ||
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. In pollution degree 2, only nonconductive pollution occurs. A temporary conductivity caused by condensation must be expected occasionally. |
Product specifications
Item | Specifications | |
---|---|---|
No. of points | 16 | |
Isolation method | Relay | |
Rated switching voltage/current | Voltage: 24VDC, 200VAC (50/60Hz), Current: 2A/1 contact (resistance load, COSφ = 1) |
|
Maximum number of simultaneous on points | 100% | |
Response time ( Off → On ) | 10ms or less (excluding programmable controller response time) | |
Response time ( On → Off ) | 12ms or less (excluding programmable controller response time) | |
Minimum switching load | 5VDC 1mA | |
Maximum switching load | 270VAC, 150VDC | |
Maximum switching frequency | 1800 times/hour (1s or longer on, 1s or longer off) | |
Mechanical life | 20 million times or more | |
Electrical life | 100000 times or more at rated switching voltage/current 100000 times or more at 200VAC 1.5A (COSφ = 0.7), 240VAC 1A (COSφ = 0.7) 100000 times or more at 200VAC 1A (COSφ = 0.35) 100000 times or more at 24VDC 1A (L/R = 7ms), 100VDC 0.1A (L/R = 7ms) |
|
Wiring method for common | 16-point independent common | |
External power supply | 24VDC+-10% (ripple ratio: within 5%) | |
Module current consumption | Approx. 90mA at 24VDC (not including current consumption of programmable controller) |
|
Withstand voltage, insulation resistance | Between inputs/outputs, between outputs: 2500VAC for 1 minute, between contacts: 750VAC for 1 minute, 10MΩ or more |
|
Noise immunity | Simulator noise 1000Vp-p, noise width 1us (based on a noise simulator with a noise frequency of 30 to 100Hz) |
|
Operation display | LED on with power supply on and output on | |
Socket | None (module irreplaceable) | |
No. of times to replace module | - | |
Module mixing | - | |
Terminal block | M3 screws, number of terminals: 34P, 7.62mm pitch, spring-up screw with finger protection cover |
|
Applicable wire, tightening torque | 0.3 to 2mm2 (with solderless terminal used), 58.8 to 88.2N·cm (6 to 9kgf·cm) | |
Module installation ( Screw type ) | M4 × 0.7mm × 22mm or more, tightening torque: 78 to 118N·cm (8 to 12kgf·cm) |
|
Module instALlation ( DIN rail ) | TH35-7.5Fe, TH35-7.5AL (IEC 60715 compliant) | |
Accessory | - | |
Weight | Approx. 230g |
External Dimensions・Product CAD Data
External Dimensions
Product CAD Data
Wiring diagrams and connection examples・Note
Wiring diagrams and connection examples
N/A
Name | Filename |
---|
Other Technical Information
N/A
Name | Filename |
---|
Precautions for use
N/A
Name | Filename |
---|
Catalogs・New Product Releases
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|---|---|---|
Digital Signal Converters (Terminal Modules)(3MB) | English | MEIC224E_226-C | February 2025 |
数字信号转换器(终端模块)(3MB) | Simplified Chinese | MEIC234C_236-A | February 2025 |
FA Goods General Catalog Digest edition(28MB) | English | MEIC198E_209-B | March 2024 |
FA关联产品 综合目录 摘要版(29MB) | Simplified Chinese | MEIC199C_209-B | March 2024 |
FA Goods General Catalog Time and Wire Saving Devices(79MB) | English | MEIC202E_20Z-E | November 2024 |
Manual
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|---|---|---|
User's Manual(8MB) | English | 50D-FG0232E-E | June 2022 |
Technical information(Technical News)
* The table can be scrolled to the right.
Name | Language | Document No. | Release date |
---|---|---|---|
Removal of CE marking from FA Goods time and wire saving devices due to abrogation of EN 50178 (EN standard)(218KB) | English | FAB3-052E | 12/22/2021 |
Downloads
N/A
Profile/module FB (function block)
Name | Filename |
---|
Control & Communication System Profile CSP+
Name | Filename |
---|
Sample program
Name | Filename |
---|
Video
N/A
Related products
Connection cables
Model | Length | Name | Overview |
---|---|---|---|
FA-FXCBL30MMH20 | 3.0m | Connection cable for 16-point input/output sink | Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable. |
FA-FXCBL10MMH20 | 1.0m | Connection cable for 16-point input/output sink | Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable. |
FA-FXCBL20MMH20 | 2.0m | Connection cable for 16-point input/output sink | Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable. |
FA-FXCBL15MMH20 | 1.5m | Connection cable for 16-point input/output sink | Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable. |
FA-FXCBL06MMH20 | 0.6m | Connection cable for 16-point input/output sink | Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable. |
FA2-CB1LT30MM1H20 | 3.0m | Connection cable for 16-point input/output sink, withstanding -20°C | Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable. |
FA2-CB1LT20MM1H20 | 2.0m | Connection cable for 16-point input/output sink, withstanding -20°C | Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable. |
Related products
- Short-circuit bar for 7.62mm pitch M3-screw terminal block(with/without insulating coating)
- FA-BAR20PG-20
The required number of short-circuit bars can be easily cut out along cutting lines.
- Short-circuit bar for 7.62mm pitch M3-screw terminal block(with/without insulating coating)
- FA-BAR20P-20
The required number of short-circuit bars can be easily cut out along cutting lines.