M3-screw, module type, 16-point 24VDC N/O contact relay input
(independent common; with socket)

FA-TH16XRA20S

Features

  • Product overview:
    Digital signals from a programmable controller can be converted to
    signals suitable for the connected devices such as a magnetic starter
    (example: from 24VDC signal to 200VAC signal).
    One terminal module supports connections with multiple devices with
    different voltage loads.
    Merit.1
    Commons can be used separately according to points used, such as 4 points/common.
    Merit.2
    Sockets enable a relay to be replaced individually.
Sales status On sale

Basic specifications

Item Specifications
Model FA-TH16XRA20S
Category Time and wire saving devices
Connected device Programmable controller
Series of connected devices MELSEC iQ-R
MELSEC iQ-F
MELSEC-Q
MELSEC-F
MELSEC-L
Product category Digital signal converter (terminal module)
Terminal block type Screw terminal type
Delivery date -

Specifications

General specifications

Item Specifications
Operating ambient temperature -20 to 55℃
Storage ambient temperature -25 to 75℃
Operating ambient humidity 5 to 95%RH, no condensation
Storage ambient humidity 5 to 95%RH, no condensation
Vibration resistance ( With intermittent vibration ) 5 to 8.4Hz : Half amplitude 3.5mm
8.4 to 150Hz : Acceleration 9.8m/s2
Number of sweeps : 10 times in each direction X, Y, and Z
Vibration resistance ( With continual vibration ) 5 to 8.4Hz : Half amplitude 1.75mm
8.4 to 150Hz : Acceleration 4.9m/s2
Shock resistance 147m/s2, 3 times in each direction X, Y, and Z(Applicable standards :JIS B 3502, IEC61131-2)
Operating atmosphere Free of corrosive gases
Operating altitude *1 2000m or less
Installation location Inside the control panel (Indoor use)
Overvoltage category *2 II or less
Pollution degree *3 2 or less
Precautions *1 Do not use or store the module under pressure higher than the atmospheric pressure at an altitude of 0 meters. Doing so may cause malfunction. When using
the module under pressure, please consult your local Mitsubishi Electric representative.
*2 This indicates the assumption that the equipment is connected to a power distribution system, ranging from a public electrical power distribution network down to machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for equipment with the rated voltage of up to 300V is 2500V.
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. In pollution degree 2, only nonconductive
pollution occurs. A temporary conductivity caused by condensation must be expected occasionally.


Product specifications

Item Specifications
Connected programmable
controller
Positive common, 24VDC input module
No. of points 16
Isolation method Relay
Rated input voltage/current Voltage: 24VDC, Current: approx. 10mA (24VDC)
Operating voltage range 21.6 to 26.4VDC (24VDC+-10% (ripple ratio: within 5%))
Maximum number of simultaneous on points 100% (3-way installation)
On voltage/On current 19.2VDC or more/8.1mA or more
Off voltage/Off current 2.4VDC or less/1.0mA or less
Input impedance Approx. 2.2kΩ
Response time ( Off → On ) 10ms or less (excluding programmable controller response time)
Response time ( On → Off ) 12ms or less (excluding programmable controller response time)
Minimum switching load 24VDC, 1mA or more
Maximum switching frequency 1800 times/hour (1s or longer on, 1s or longer off)
Mechanical life 20 million times or more
Electrical life 100000 times or more when energized by 24VDC, 100mA (contact side)
Wiring method for common 16-point independent common
External power supply 24VDC+-10% (ripple ratio: within 5%)
Module current consumption Approx. 10mA at 24VDC (not including current consumption of programmable controller)
Withstand voltage, insulation resistance Between inputs, between external power supply and input: 2500VAC for 1 minute, 10MΩ or more
Noise immunity Simulator noise 500Vp-p, noise width 1us
(based on a noise simulator with a noise frequency of 25 to 60Hz)
Operation display LED on with power supply on and input on
Socket Yes (relay module replaceable)
No. of times to replace module 50 times
Terminal block M3 spring-up screws, number of terminals: 34P, 7.62mm pitch
Applicable wire,
tightening torque
0.3 to 2mm2 (with solderless terminal used), 58.8 to 88.2N·cm (6 to 9kgf·cm)
Module installation ( Screw type ) M4 × 0.7mm × 22mm or more, tightening torque: 78 to 118N·cm (8 to 12kgf·cm)
Module installation ( DIN rail ) TH35-7.5Fe, TH35-7.5Al (IEC 60715 compliant)
Accessory Module extraction tool
Weight Approx. 300g
Precautions When connecting cables to the module, push the cable connector until it is locked. Failure to do so may cause poor contact.

Wiring diagrams and connection examples・Note

Wiring diagrams and connection examples

N/A

Name Filename

Other Technical Information

N/A

Name Filename

Precautions for use

N/A

Name Filename

Catalogs・New Product Releases

* The table can be scrolled to the right.

Name Language Document No. Release date
MELSEC系列专用 中继端子排(861KB) Simplified Chinese MEIC230C_22X-A February 2025
Digital Signal Converters (Terminal Modules)(3MB) English MEIC224E_226-C February 2025
数字信号转换器(终端模块)(3MB) Simplified Chinese MEIC234C_236-A February 2025
FA Goods General Catalog Digest edition(28MB) English MEIC198E_209-B March 2024
FA关联产品 综合目录 摘要版(29MB) Simplified Chinese MEIC199C_209-B March 2024
FA Goods General Catalog Time and Wire Saving Devices(79MB) English MEIC202E_20Z-E November 2024

Manual

* The table can be scrolled to the right.

Name Language Document No. Release date
User's Manual(4MB) English 50D-FG0233E-C June 2022
EMC and Low Voltage Directives Compliant Manual(256KB) English 50D-FA9010-108E-G December 2023

Technical information(Technical News)

N/A

* The table can be scrolled to the right.

Name Language Document No. Release date

Downloads

N/A

Profile/module FB (function block)

Name Filename

Control & Communication System Profile CSP+

Name Filename

Sample program

Name Filename

Video

N/A

Related products

Connection cables

Model Length Name Overview
FA-CBL50YM20 5m For MELSEC terminal block I/O (Y-shaped solderless terminals and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL06FM2V 0.6m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) A round 40-core cable is pulled out from a MELSEC series FCN 40P connector type I/O module. The other cable end branches into two MIL 20P connectors, each of which is connected to a MELSEC-dedicated 16-point terminal block.
FA-CBL10FM2V 1m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) A round 40-core cable is pulled out from a MELSEC series FCN 40P connector type I/O module. The other cable end branches into two MIL 20P connectors, each of which is connected to a MELSEC-dedicated 16-point terminal block.
FA-CBL50FM2V 5m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) A round 40-core cable is pulled out from a MELSEC series FCN 40P connector type I/O module. The other cable end branches into two MIL 20P connectors, each of which is connected to a MELSEC-dedicated 16-point terminal block.
FA-CBL100FM2V 10m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) A round 40-core cable is pulled out from a MELSEC series FCN 40P connector type I/O module. The other cable end branches into two MIL 20P connectors, each of which is connected to a MELSEC-dedicated 16-point terminal block.
FA-CBL20FM2V 2m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) A round 40-core cable is pulled out from a MELSEC series FCN 40P connector type I/O module. The other cable end branches into two MIL 20P connectors, each of which is connected to a MELSEC-dedicated 16-point terminal block.
FA-CBL30FM2V 3m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) A round 40-core cable is pulled out from a MELSEC series FCN 40P connector type I/O module. The other cable end branches into two MIL 20P connectors, each of which is connected to a MELSEC-dedicated 16-point terminal block.
FA-CBL20FM2H 2m For positive common input/sink output of Mitsubishi Electric CC-Link remote I/O module (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL30FM2H 3m For positive common input/sink output of Mitsubishi Electric CC-Link remote I/O module (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL03FM2H 0.3m For positive common input/sink output of Mitsubishi Electric CC-Link remote I/O module (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL10FM2H 1m For positive common input/sink output of Mitsubishi Electric CC-Link remote I/O module (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL15FM2V 1.5m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on MIL 20P connector side) A round 40-core cable is pulled out from a MELSEC series FCN 40P connector type I/O module. The other cable end branches into two MIL 20P connectors, each of which is connected to a MELSEC-dedicated 16-point terminal block.
FA-CBL30YM20 3m For MELSEC terminal block I/O (Y-shaped solderless terminals and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL20YM20 2m For MELSEC terminal block I/O (Y-shaped solderless terminals and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL20M20 2m For MELSEC terminal block I/O (discrete cable and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL10YM20 1m For MELSEC terminal block I/O (Y-shaped solderless terminals and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL06M20 0.6m For MELSEC terminal block I/O (discrete cable and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL10M20 1m For MELSEC terminal block I/O (discrete cable and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL30TMV20 3m For MELSEC terminal block I/O (MELSEC-Q terminal block and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL10TMV20 1m For MELSEC terminal block I/O (MELSEC-Q terminal block and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL06TMV20 0.6m For MELSEC terminal block I/O (MELSEC-Q terminal block and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL20TMV20 2m For MELSEC terminal block I/O (MELSEC-Q terminal block and MIL 20P connector) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL20FM2LH 2m For positive common input/sink output of Mitsubishi Electric CC-Link remote I/O module (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL30FM2LH 3m For positive common input/sink output of Mitsubishi Electric CC-Link remote I/O module (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL10FM2LH 1m For positive common input/sink output of Mitsubishi Electric CC-Link remote I/O module (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL50FM2LH 5m For positive common input/sink output of Mitsubishi Electric CC-Link remote I/O module (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL50FM2LV 5m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL100FM2LV 10m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL20FM2LV 2m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL30FM2LV 3m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL10FM2LV 1m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.
FA-CBL06FM2LV 0.6m For MELSEC positive common input/sink output (FCN 40P connector and two MIL 20P connectors, branching on programmable controller side) Easy wiring, reducing wiring time : A programmable controller and a junction terminal block can be easily wired using the dedicated cable.

Related products

MELSEC-dedicated 16-point 3-wire open type with 4-pole connector
FA-LEB16XY-D

The junction terminal block helps signal transmissions between a
programmable controller and devices such as sensors in connection
methods suitable for applications.

MELSEC-dedicated 16-point 3-wire open type with 4-pole connector
FA-LEB16XY

The junction terminal block helps signal transmissions between a
programmable controller and devices such as sensors in connection
methods suitable for applications.

Module extraction tool
FA-PULL10

These tools are used to pull out modules from a socket-type terminal module.

Replacement module
FA-NYP24WK4

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

Replacement module
FA-NYBP24WK4

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

M3.5-screw 16-point 100VAC photocoupler input (2-wire type, 16 points/common)
FA-TH16X100A31L

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

M3.5-screw 16-point 48VDC photocoupler input (2-wire type, 16 points/common)
FA-TH16X48D31L

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

M3.5-screw 16-point 100VDC photocoupler input (2-wire type, 16 points/common)
FA-TH16X100D31L

Positive common, 24VDC input module

M3.5-screw 16-point 24VDC photocoupler input (2-wire type, 16 points/common)
FA-TH16X24D31L

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

M3.5-screw 16-point 200VAC photocoupler input (2-wire type, 16 points/common)
FA-TH16X200A31L
FA-TH16X200A31L

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

M3-screw 16-point 24VDC photocoupler input (2-wire type, 16 points/common)
FA-TH16X24D31

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

M3-screw 16-point 100VAC photocoupler input (2-wire type, 16 points/common)
FA-TH16X100A31

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

M3-screw 16-point 200VAC photocoupler input (2-wire type, 16 points/common)
FA-TH16X200A31

Digital signals from a programmable controller can be converted to
signals suitable for the connected devices such as a magnetic starter
(example: from 24VDC signal to 200VAC signal).
One terminal module supports connections with multiple devices with
different voltage loads.

Short-circuit bar for 7.62mm pitch M3-screw terminal block(with/without insulating coating)
FA-BAR20P-20

The required number of short-circuit bars can be easily cut out along cutting lines.

Short-circuit bar for 7.62mm pitch M3-screw terminal block(with/without insulating coating)
FA-BAR20PG-20

The required number of short-circuit bars can be easily cut out along cutting lines.

MELSEC-dedicated 16-point 1-wire type
FA-TB16XY

The junction terminal block helps signal transmissions between a programmable controller and devices such as sensors in connection methods suitable for applications.

MELSEC-dedicated 16-point 1-wire type
FA1-TE1SV16XY

The junction terminal block helps signal transmissions between a programmable controller and devices such as sensors in connection methods suitable for applications.

MELSEC-dedicated 16-point 3-wire type (16 points/8 (24V) common points + 8 (0V) common points)
FA-TB16XYPN

The junction terminal block helps signal transmissions between a programmable controller and devices such as sensors in connection methods suitable for applications.

MELSEC-dedicated 16-point 3-wire type
(16 points/16 (24V) common points + 16 (0V) common points)
FA-TB16XYPN3